4.4 Auto / manual mode of operation
Note:
Enable the manual mode by
entering access code 22.
The operating modes remains in
effect even after a power failure.
The manual mode takes
precedence over any other
automatic function (hold).
Hardware locking in the manual
mode is not possible.
The manual settings remain in
effect until they are actively reset.
Error code E102 is signalled in the
manual mode.
Auto mode
In this mode of operation, the relays are controlled by the transmitter.
REL key
In manual mode, the REL key is used to select one of the relays or the
cleaning function present in the instrument.
Switching to manual mode
The instrument is switched to the manual mode for relay setting by
pressing the following keys:
Press AUTO key.
Enter code 22. Confirm with ENTER key.
Select relay or function. Press the REL key to toggle between the relays.
The display shows the selected relay and the switching status (ON /
OFF) in the second line. In manual mode, the measuring value is
continuously displayed(e.g. for monitoring during dosage).
Set the relays. Switch on with PLUS, switch off with MINUS. The relay
state remains in effect until it is actively reset.
Press AUTO key for returning to the measuring mode.
All relais are controlled by the transmitter again.